Heat Pump

Daikin Heat Pump error codes

59 codes across 1 model family. Start with your model number, because Daikin reuses the same numbers for different faults on different boards.

Daikin shares code tables with other brands

Daikin furnaces use Goodman control platforms, so Goodman model families apply. Daikin VRV IV heat pumps and Daikin mini split and thermostat codes are entirely separate systems with their own code tables.

Find your model family

The model number is on the data plate, usually on the side or back of the unit or behind the service panel. It usually starts with the letters or numbers in the name below.

VRV IV RXTQ-TA / RXTQ-TB

Daikin VRV IV RXTQ heat pump codes

59 codes

59 codes

The RXTQ outdoor unit serves VRV indoor units over a shared communication bus, and the factory splits the code list by which unit reports it. A and C codes come from indoor units, E, F, H, J, L and P from the outdoor unit, and U and M are system or centralized controller faults. This is a commercial and light commercial multi split platform, not a residential one indoor mini split unit.

Daikin VRV IV RXTQ-TA / RXTQ-TB heat pump error codes, what each one means and how urgent it is
CodeWhat it meansHow urgent
A0Indoor unit external protection device abnormalityHigh
A1Indoor unit control board abnormalityHigh
A3Drain level control system abnormalityModerate
A6Indoor fan motor lock or overloadHigh
A7Swing flap motor abnormality, warningLow
A8Indoor unit power supply voltage abnormalityHigh
A9Indoor unit electronic expansion valve abnormalityHigh
AFDrain water level above the limit, warningLow
AHSelf cleaning decoration panel abnormalityModerate
AJCapacity setting errorModerate
C1Transmission abnormality between the indoor and fan boardsHigh
C4Indoor heat exchanger liquid pipe thermistor abnormalityModerate
C5Indoor heat exchanger gas pipe thermistor abnormalityModerate
C6Indoor unit and fan board combination errorHigh
C9Suction air thermistor abnormalityModerate
CADischarge air thermistor abnormalityModerate
CCHumidity sensor system abnormality, warningLow
CEInfrared presence or floor sensor error, warningLow
CJRemote controller thermistor abnormality, warningLow
E1Outdoor unit main board abnormalityHigh
E3High pressure switch activationHigh
E4Low pressure protection activationHigh
E5Compressor motor lockHigh
E7Outdoor fan motor abnormalityHigh
E9Outdoor electronic expansion valve abnormalityHigh
F3Discharge pipe temperature abnormalityHigh
F6Refrigerant overchargeHigh
H9Outdoor air thermistor abnormality, R1TModerate
J3Discharge pipe thermistor abnormality, R2TModerate
J5Suction pipe thermistor abnormality, R3T and R5TModerate
J6Outdoor heat exchanger deicer thermistor abnormality, R4TModerate
J7Outdoor heat exchanger liquid pipe thermistor abnormality, R7TModerate
J9Subcooling heat exchanger gas pipe thermistor abnormality, R6TModerate
JAHigh pressure sensor abnormalityHigh
JCLow pressure sensor abnormalityHigh
L1Inverter board abnormalityHigh
L4Radiation fin temperature rise abnormalityHigh
L5Compressor instantaneous overcurrentHigh
L8Compressor overcurrentHigh
L9Compressor startup abnormalityHigh
LCTransmission error between the outdoor board microcomputersHigh
P1Inverter circuit capacitor high voltageHigh
P4Radiation fin thermistor abnormality, warningLow
U0Refrigerant shortage, warning that should not be ignoredHigh
U2Power supply insufficient or instantaneous abnormalityHigh
U3Check operation not executedModerate
U4Transmission error between indoor and outdoor unitsHigh
U5Transmission error between the controller and the indoor unitModerate
U8Transmission error between main and sub controllersModerate
U9Transmission error within the same systemHigh
UAImproper indoor and outdoor unit combinationHigh
UCCentralized controller address duplication, warningLow
UETransmission error between the centralized controller and an indoor unitHigh
UFSystem not set yetModerate
UHSystem address undefinedHigh
M1Centralized controller board defectHigh
M8Transmission error between centralized controllersModerate
MAPoor centralized controller combinationModerate
MCAddress duplication and poor setting, warningLow
Open the VRV IV RXTQ-TA / RXTQ-TB code list →

Common questions

How many Daikin heat pump error codes are documented here?
59 codes across 1 model family. Every code page lists what the fault means, the causes, the checks you can safely do yourself, and when it stops being worth resetting the unit.
How do I read the code on a Daikin heat pump?
The control board prints the code as text, so you read it off the display rather than counting anything. Write the exact characters down, including any letter, because Daikin codes are short and easy to misread.
Which Daikin heat pump model do I have?
The model number is on the data plate, usually on the side or back of the unit or behind the service panel. The family on this page are VRV IV RXTQ-TA / RXTQ-TB. The model number starts with the letters or numbers in that name, which is the only reliable way to pick the right code table.
Do other brands share Daikin heat pump codes?
Daikin furnaces use Goodman control platforms, so Goodman model families apply. Daikin VRV IV heat pumps and Daikin mini split and thermostat codes are entirely separate systems with their own code tables.